This paper focused on developed simulation models of energy supply systems such as combined heat and power (CHP), district heating and cooling (DHC), storage battery, thermal storage tank, and power s...ystem model. This paper estimated energy saving effect by the diffusion of these systems in Japanese commercial districts. The developed models in this paper calculated each operation at five-minute intervals and used heat supply piping length, transport power, and piping heat loss in DHC calculations. The estimation of the energy saving effect by the energy supply systems based on five-minute energy demand in individual buildings confirmed the energy saving effect of DHC and the energy storage systems in Japanese commercial districts.続きを見る
|