<紀要論文>
APPLICATION OF HEAT PUMP SYSTEM TO THE AIR TEMPERATURE CONTROL IN GROWTH CHAMBER

作成者
本文言語
出版者
発行日
雑誌名
開始ページ
終了ページ
出版タイプ
アクセス権
概要 The heat pump system with a comparator and a blind controller was applied to the air temperature control in a growth chamber. Settling time in step response, the accuracy in the fixed command control ...of air temperature and the power requirements of the control were examined. It was found in the characteristics that the response times are relatively short, and the accuracies are about ±1℃. The system was simpler and able to be driven with smaller power requirements, as compared with the other prevailed systems. Thus, the construction cost and the running energy were extremely low. From these facts, it was suggested that the heat pump system is useful for the air temperature control in the growth chamber.続きを見る

本文情報を非表示

KJ00004506764 pdf 312 KB 148  

詳細

レコードID
査読有無
関連情報
主題
ISSN
NCID
タイプ
登録日 2009.04.22
更新日 2017.06.13