<学術雑誌論文>
Performance Comparison of Different Desiccant Material Based Wheels for Air Conditioning Application
作成者 | |
---|---|
本文言語 | |
出版者 | |
発行日 | |
収録物名 | |
巻 | |
号 | |
開始ページ | |
終了ページ | |
出版タイプ | |
アクセス権 | |
Crossref DOI | |
権利関係 | |
概要 | The purpose of this study is to compare different desiccant materials based desiccant wheel for air conditioning applications using a mathematical model. Seven desiccant material wheels are categorize...d into three groups. The results revealed that the desiccant wheel made of group 2 materials has a higher temperature-difference in comparison to other groups. So, these desiccant wheels cannot be recommended for air-conditioning applications. For higher ranges of process inlet temperature (40 to 50℃), moisture removal obtained from group 2 wheels is higher than the other wheels and also obtains approximately similar ΔT. But in lower ranges of process inlet temperature (10 to 20℃), group 3 wheels give higher MR with moderate ΔT. although the temperature difference is higher but, due to the higher moisture removal, group 3 wheels can be the preferable choice.続きを見る |
目次 | 1. Introduction 2. Mathematical model 3. Validation of mathematical model with experimental results 4. Results and discussion 5. Conclusions 6. Future work scope |